Commissioning Ethernet switch (MM) FN2008-A1

Connecting 'Sites' physically to one another
13 Commissioning Ethernet switch (MM)
46
Building Technologies
Fire Safety
FN2008-A1
This description focuses on correctly integrating the 'Ethernet switch (MM)
FN2008-A1' in the fire detection installation. More information about the product
can be found on the data carrier in the scope of supply and at the following
address: http://support.automation.siemens.com (Manufacturer designation:
Scalance X204-2)
NOTICE
Alternate products for 'Ethernet switch (MM) FN2008-A1'
No compliance with EN 54
For an EN-54-compliant fire detection installation, you must use the permitted
'Ethernet switch (MM) FN2008-A1'.
The 'Ethernet switch (MM) FN2008-A1' is a class A equipment and may cause
radio interference in residential areas. If interference does occur, observe the
relevant information in document A6V10210390. See chapter 'Applicable
documents'.
Commissioning
1. Install the 'Primary Setup Tool' software. Link [
2. Assign the IP address. Link [
3. Configure FN2008-A1 using the Internet browser Link [
4. In Cerberus-Engineering-Tool, create the links you want e.g. for the following
monitoring functions in a 'Technical zone'.
-
Redundant power
-
Display error contact
You will find detailed instructions on creating a link in document A6V10210424
See chapter 'Applicable documents'.
The FN2008-A1 has no IP address in the factory setting. You must manually
assign the IP address.
See also
Applicable documents [
47]
47]
8]
48]
A6V10210416_f_en_--
14.01.2013