Rectify Localization Errors; Checking 'Site' Function - Siemens FS720 Commissioning, Maintenance, Troubleshooting

Fire detection system
Table of Contents

Advertisement

6.18
6.19
Building Technologies
Fire Safety
Element
Area
Section
Zone
Commands under 'Execute commands'
You can also switch to normal operation at superordinate level for the command
in question. Test mode can also be exited in the 'Zone', 'Section' or 'Area', for
example.
'Switching 'Zone' to normal operation
There is a shortened procedure for switching individual 'Zones' to normal operation:
1. Select 'Message summary' > 'Test message' in the main menu.
2. Select the displayed 'Zone' in test mode and press the 'Execute Commands'
softkey.
3. Select the 'Detector test END' command.
The 'Zone' is switched to normal operation.
The yellow 'DETECTORES EN PRUEBAS' LED goes out.

Rectify localization errors

1. Use 'Topology' > 'Hardware tree' > 'Station' > 'Line card' > 'Detector line' to
select the corresponding detector line in the main menu.
2. Press the 'More Options' softkey and select 'Execute commands'.
3. Select the 'Accept replaced devices' command.
The fault messages are no longer displayed.
If devices are missing or the device types do not correspond to the C-NET
topology, error messages will continue to be displayed.

Checking 'Site' function

Test the functions of the 'Site' in the various test modes:
You will find information about testing a 'Site' in the chapter 'Testing' in document
A6V10211076. See chapter 'Applicable documents'.
See also
Applicable documents [
General commissioning steps
Rectify localization errors
Command
'Non-MCP zones det.test END'
'MCP zones det.test END'
'Non-MCP zones det.test END'
'MCP zones det.test END'
'Detector test END'
8]
6
33
A6V10210416_f_en_--
14.01.2013