20.7.2
Building Technologies
Fire Safety
Updating the firmware of the main CPU and the additional CPUs
10. Click on 'Close' in the 'FW update main and additional CPUs' window.
The following window is opened:
11. On the 'Station', set the 'S38-2' switch to 'OFF'.
The 'Station' is restarted many times. This procedure takes up to ten
minutes.
12. Click on 'OK' in the 'Information' window.
After the restart, the 'Station' display shows the available BDVs. It is not
necessary to install a BDV at this point.
Initializing the 'Station' instead of installing the BDV saves time. During
initialization, the BDV and the configuration data are loaded to the 'Station'.
PMI & mainboard FCM2027
Familiarize yourself with the information in the chapter 'Preparation and
security'.
1. Select 'Update' > 'FW update main and additional CPUs' from the menu bar.
2. If the 'Password check' window is open, enter the password '1234' and click on
'OK'.
The 'Confirmation' window opens.
3. NOTICE! Data loss. Save the configuration data before updating the firmware.
4. Click on 'Yes'.
The 'FW update main and additional CPUs' window opens.
Updating the firmware of the 'Station'
A6V10210416_f_en_--
20
81
14.01.2013