Index 8030 AI settings Ch.2 (parameterization of channel 2)
Index (hex) Name
8030:0
AI Settings Ch.2
8030:01
Enable user scale
8030:06
Enable filter
8030:07
Enable limit 1
8030:08
Enable limit 2
8030:0A
Enable user calibra-
tion
8030:0B
Enable vendor cali-
bration
8030:11
User scale offset
8030:12
User scale gain
8030:13
Limit 1
8030:14
Limit 2
8030:15
Filter settings
8030:17
User calibration offset
8030:18
User calibration gain
8030:19
Range
EP3744-0041 and EP3744-1041
Meaning
Maximum subindex
1
User scale is active.
1
Enable filter, which makes PLC-cycle-synchronous
data exchange unnecessary
1
Limit 1 enabled
1
Limit 2 enabled
1
Enabling of the user calibration
1
Enabling of the vendor calibration
User scale offset
User scale gain.
The gain is represented in fixed-point format, with the
-16
factor 2
.
The value 1 corresponds to 65535
and is limited to +/- 0x7FFFF
First limit value for setting the status bits
Second limit value for setting the status bits
This object shows the digital filter settings. The filter set-
tings can only be read here. They are set via channel 1
for all channels of the module.
0
50 Hz FIR
1
60 Hz FIR
2
IIR 1
3
IIR 2
4
IIR 3
5
IIR 4
6
IIR 5
7
IIR 6
8
IIR 7
9
IIR 8
Permissible values:
8
Differential pressure measurement relative to the
reference sensor
7
Absolute pressure measurement
Version: 2.2
Commissioning/Configuration
Data type
UINT8
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
INT32
INT32
(0x00010000
)
dez
hex
INT16
INT16
UINT16
INT32
INT16
UINT16
Flags
Default
RO
0x19 (25
)
dec
RW
0x00 (0
)
dec
RW
0x01 (1
)
dec
RW
0x00 (0
)
dec
RW
0x00 (0
)
dec
RW
0x00 (0
)
dec
RW
0x01 (1
)
dec
RW
0x00000000
(0
)
dec
RW
0x00010000
(65536
)
dec
RW
0x0000 (0
)
dec
RW
0x0000 (0
)
dec
RW
0x0000 (0
)
dec
RW
0x00000000
(0
)
dec
RW
0x4000
(16384
)
dec
RW
0x0008 (8
)
dec