VLT HVAC Low Harmonic Drive Operating In-
structions
4.3.10 IP21 Drip Shield Installation (Frame size D)
To comply with the IP21 rating, a separate drip shield is to be
installed as explained below:
Remove the two front screws
Insert the drip shield and replace screws
Torque the screws to 5,6 Nm (50 in-lbs)
NB!
Drip shield is necessary on both filter and drive section.
Illustration 4.26: Drip shield installation.
®
MG.16.A1.02 - VLT
is a registered Danfoss trademark
4 How to Install
4
39