6 How to Programme the Low Harmonic Drive
6-10 Terminal 53 Low Voltage
Range:
0.07 V*
[Application dependant]
6-11 Terminal 53 High Voltage
Range:
10.00 V*
[Application dependant]
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
0.000 N/A*
[-999999.999 - 999999.999 N/A]
6-15 Terminal 53 High Ref./Feedb. Value
6
Range:
Application
[-999999.999 - 999999.999 N/A]
dependent*
6-16 Terminal 53 Filter Time Constant
Range:
0.001 s*
[0.001 - 10.000 s]
6-17 Terminal 53 Live Zero
Option:
[0]
Disabled
[1] *
Enabled
6-20 Terminal 54 Low Voltage
Range:
0.07 V*
[Application dependant]
6-21 Terminal 54 High Voltage
Range:
10.00 V*
[Application dependant]
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
0.000 N/A*
[-999999.999 - 999999.999 N/A]
106
Function:
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
Terminal 53 Low Ref./Feedb. Value .
feedback value set in par. 6-14
Function:
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par. 6-15
Function:
Enter the analog input scaling value that corresponds to the low voltage/low current set in
par. 6-10
Terminal 53 Low Voltage and par. 6-12 Terminal 53 Low Current .
Function:
Enter the analog input scaling value that corresponds to the high voltage/high current value set in
Terminal 53 High Voltage and par. 6-13 Terminal 53 High Current .
par. 6-11
Function:
Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
electrical noise in terminal 53. A high time constant value improves dampening but also increases
the time delay through the filter.
This parameter cannot be adjusted while the motor is running.
Function:
This parameter makes it possible to disable the Live Zero monitoring. E.g. to be used if the analog
outputs are used as part of a de-central I/O system (e.g. when not as part of any frequency con-
verter related control functions, but feeding a Building Management system with data).
Function:
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
feedback value, set in par. 6-24
Terminal 54 Low Ref./Feedb. Value .
Function:
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par. 6-25
Function:
Enter the analog input scaling value that corresponds to the low voltage/low current value set in
Terminal 54 Low Voltage and par. 6-22 Terminal 54 Low Current .
par. 6-20
®
MG.16.A1.02 - VLT
is a registered Danfoss trademark
VLT HVAC Low Harmonic Drive Operating In-
Terminal 53 High Ref./Feedb. Value .
Terminal 54 High Ref./Feedb. Value .
structions