Assa Abloy Sargent Profile Series Installation Instructions Manual page 5

Poe exit device
Hide thumbs Also See for Sargent Profile Series:
Table of Contents

Advertisement

Profile Series v.S1 PoE Exit Device
Installation Wiring (Continued)
Frame Harness Installation
A
Supplied by CI
B-Splice
Crimp Connector
Ceiling
24AWG
Stranded
Wire for
Earth
Ground
inside
15' Frame
Harness
Frame-Side
Harness
Assembly
(15' length)
Cable
drain wire
concealed
in shrink
tubing
Molex-M
PoE Data Hinge
B
4-pin M
6-pin M
Frame
Components and wire harness supplied by McKinney: Suggested installation.
Cut end / ceiling-side PoE harness:
RJ45-M
Do not confuse pair numbers with pin numbers. A pair number is used for refer-
ence only (eg: 10Base-T Ethernet uses pairs 2 & 3). The pin numbers indicate
actual physical locations on the plug and jack.
Hinge side of PoE harness:
1. Feed cut end of harness into hole on hinge-side through single access hole.
2. Push one connector back through the hole and feed into the other access hole.
Each of the hinge-side harness connectors should end up threaded through
a different access hole and matched to the same size pin connector from
the door harness:
• 4-pin male molex connector.
• 6-pin male molex connector with ground wire.
4-pin F
Drain Wire
6-pin F
PoE Hinge (Patent Pending)
TIA-568-B Standard Wiring
Pair Number
1
White/Blue
2
White/Orange
3
White/Green
4
White/Brown
Hinge-side harness connectors:
• 4-pin male molex connector
• 6-pin male molex connector with ground wire
Lock-side harness connectors:
• Ring terminal
• (2) 4-pin connectors
1-800-810-WIRE • www.sargentlock.com • A7765C
Wire
PIN
White/Blue
5
Blue
4
White/Orange
1
Orange
2
White/Green
3
Green
6
White/Brown
7
Brown
8
5