La Sensitivity Adjustment; Figure 12 La Alarm Limits - M&C PSS Series Instruction Manual

Portable gas conditioning unit
Hide thumbs Also See for PSS Series:
Table of Contents

Advertisement

15.2

LA Sensitivity adjustment

The sensitivity can be changed by following these steps:
1. Enter the PIN (see chapter "12.2 PIN Entry").
2. Tap and hold the
3. The display shows the code entry.
The default value is 2 and can be changed from 1 to 7. The sensitivity corresponds to the switching
threshold for the alarm and is to be understood as follows:
Sensor state
Sensitivity
Dry
0 %
7
30 %
6
40 %
5
50 %
4
60 %
3
70 %
2
80 % (Standard)
1
90 %
Wet
100 %
The cancellation limit is always 15 % below the sensitivity limit. If the sensitivity value of 2 is not changed,
the alarm is triggered at 80 % and is automatically cancelled as soon as it falls below 65 %.
The following diagram illustrates the correlations:
LA-
LA alarm at
value
default setting 2
Figure 12
LA alarm limits
30
-key for a short moment.
Enter the code "011" to change the sensitivity of the liquid sensor.
Electrical conductivity
≈50 µS/cm
≈300 µS/cm
Canceled: LA alarm at
default setting 2
LA cable break
alarm is actived
PSS-5C | 1.02.02
Wet (100 %)
1
2
2. Cancelation
3
4
5
6
7
Dry (0 %)
Alarm limit for
cable b reak and
can celation
Open
LA cable break
alarm is canceled
t
www.mc-techgroup.com

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pss-5cPss-5/2cPss-5/3c

Table of Contents