Juniper MX240 Hardware Manual page 436

Universal routing platform.
Hide thumbs Also See for MX240:
Table of Contents

Advertisement

4 alarms currently active
Alarm time Class Description 2013-01-11 14:48:26 UTC Minor PEM 0 Dipswitch 0
Feed Connection 2
3. If the show chassis alarms output shows an alarm on Dipswitch, issue the show chassis power command
to check the DIP switch position.
# run show chassis power
PEM 0:
State: Online
AC input: OK (1 feed expected, 2 feed connected)
Capacity: 4100 W (maximum 4100 W)
DC output: 855 W (zone 0, 15 A at 57 V, 20% of capacity)
In this example, the DIP switch is in the wrong position since there is one AC feed expected but two
AC feeds are connected. Change the DIP switch to position 1. This should clear the alarm.
NOTE:
Changing the DIP switch position does not impact traffic. However, it is always
recommended to do so in a maintenance window.
SEE ALSO
MX240 AC Power Supply Description | 47
MX240 DC Power Supply Description | 55
Troubleshooting the MX240 Components | 425
Replacing an MX240 AC Normal-Capacity Power Supply | 384
Replacing an MX240 DC Normal-Capacity Power Supply | 388