Communication Interfaces; Canopen Interface - Festo CPX-CEC-C1 Electronic Manual

Codesys controller for cpx terminal.
Hide thumbs Also See for CPX-CEC-C1:
Table of Contents

Advertisement

2. Installation
2.6

Communication interfaces

2.6.1 CANopen interface

Plug
Pin
1
2
3
4
5
6
7
8
9
Housing
(plug)
1)
If a drive controller with external voltage supply is connected, CAN ground (optional),
pin 6 cannot be used on the CPX−CEC−C1.
2)
FE: Functional earthing
Tab. 2/5:
Pin assignment for the CANopen interface
Festo P.BE−CPX−CEC−EN en 0907NH
On the CPX−CEC−C1, there is a CANopen interface for
connection of CAN bus slaves.
The CANopen interface is designed as a 9−pin Sub−D plug.
Signal
Internal
contacts
n.c.
CAN_L
CAN_GND
n.c.
CAN_SHLD
CAN_GND
CAN_H
n.c.
n.c.
FE
The connected CAN bus slaves are not supplied with power
over the CANopen interface.
Explanation
not connected
CAN low
CAN ground
not connected
Connection to functional earth (FE)
CAN ground (optional)
CAN high
not connected
not connected
The plug housing must be connected
2)
to FE
2)
1)
2−11