CP-Parameter
CP.34 Source of rotation direction
The source rotation setting and the mode of evaluating the rotation setting is defined
with this parameter (Enter-Parameter). With CP.34 one does not modify the rotation
source of the fixed frequencies (CP.19... 21).
Value Function
0/1
Only application mode
2
Setting by way of terminal strip forward/reverse; negative set values are set
to zero (factory setting)
3
Setting by way of terminal strip forward/reverse; the signs of the setpoint
values have no effect on the direction of rotation
4
Setting by way of terminal strip run/stop (X2A.14) and forward/reverse
(X2A.15); negative values are set to zero
5
Setting by way of terminal strip run/stop (X2A.14) and forward/reverse;
the signs of the setpoint values have no effect on the direction of rotation
6
Set value dependent, positive value - clockwise rotation; negative value
counterclockwise rotation; with set value „0" it is switched into status
„Low speed" (LS)
7
Set value dependent, positive value - clockwise rotation; clockwise rotation
is indicated
8/9
Only application mode
CP.35 AN1 Set value selection
The set value input 1 (AN1) at the F5-GENERAL control can be triggered by various
signal levels. In order to correctly evaluate the signal, this parameter must be adapted
to the signal source. At the F5-BASIC control the signal source may not be re-adjusted.
Value Reference signal
0
0...±10 V DC / Ri = 56 kOhm
1
0...+20 mA DC / Ri = 250 Ohm
2
4...20 mA DC / Ri = 250 Ohm
GB - 52