CP.28 Reaction of external overtemperature
This parameter determines the response of the drive on the external temperature
monitoring (factory setting = off). In order to activate this function the power circuit
terminals T1/T2 must be connected in accordance with the instruction manual Part 2.
After that the response can be adusted according to following table. If overheat no longer
exists, the message E.ndOH (or A.ndOH) is output. Only then the error can be reset or
the automatic restart can be carried out.
CP.28 Display Reaction
0
E.dOH Immediate disabling of modulation
1*
A.dOH Quick stopp. / disabling of modul. after reaching speed 0
2*
A.dOH Quick stopping/holding toruqe at speed 0
3
A.dOH Immediate disabling of modulation
4*
A.dOH Quick stopp. / disabling of modul. after reaching speed 0
5*
A.dOH Quick stopping/holding torque at speed 0
6*
keine No effect on the drive; With CP.31/32 = 9 an external
7
keine No effect on the drive; !No malfunction! External
*) If the motor is still too hot after 10 seconds, the error E.dOH is triggered and the
modulation is switched off!
CP.29 Analog output 1 / Function
CP.32 defines the function of analog output 1.
Value
0
1
2
3
4
5
6
7
8-10
11
12
13
14-18
19
20
GB - 50
module can be controlled (e. g. fan)
Temperature monitoring is not activated.
Function
absolute actual frequency CP.3
absolute set frequency CP.2
actual frequency CP.3
set frequency CP.2
output voltage CP.9
DC voltage CP.7
apparent current CP.4
active current ru.17
application mode only
absolute active current ru.17
power mod. temperature ru.38
motor temperature ru.46
application mode only
ramp output frequency ru.2
absolute ramp output frequency ru.2
Standardization 0...100 % (±100 %)
0...100 Hz
0...100 Hz
0...±100 Hz
0...±100 Hz
0...500 V
0...1000 V
0...2 • Irated
0...2 • ±Irated
0...2 • Irated
0...100°C
0...100 °C
0...±100 Hz
0...100 Hz
Restart
Remove fault;
Actuate
reset
autom. reset,
if fault is no
longer present
- inapplicable -