Bypass Input Electrical Specifications; Battery Specifications; Output Electrical Specifications - Huawei UPS5000-E Series User Manual

Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(40 kVA-128 kVA)
User Manual (Integrated UPS 2.0)

10.5 Bypass Input Electrical Specifications

Item
Input system
Rated input voltage
Input frequency

10.6 Battery Specifications

Item
Battery voltage
Battery management
Cold start
Charge voltage

10.7 Output Electrical Specifications

Item
Output system
Voltage
Frequency
Output PF
Transfer time
Issue 04 (2018-04-20)
UPS5000-E-40K/80K/120K/128K
Three-phase, four-wire, PE wire
380 V AC, 400 V AC, or 415 V AC (line voltage)
50/60 Hz ± 6 Hz (adjustable with the tolerance of 0.5–6 Hz, ± 2
Hz by default).
Copyright © Huawei Technologies Co., Ltd.
UPS5000-E-40K/80K/120K/128K
360–528 V DC (30–44 batteries, 32 by default; 6%
derated when 30 batteries are configured)
Intelligent battery management
In the case of a mains failure, batteries can start the
UPS to power loads
Equalized voltage: 2.35 V/cell
Float voltage: 2.25 V/cell
UPS5000-E-40K/80K/120K/128K
Three-phase, four-wire, PE wire
380 V AC, 400 V AC, or 415 V AC (tolerance ± 1%)
(line voltage)
In normal mode, the mains frequency is
synchronized with the bypass input frequency.
In battery mode, the frequency is 50 Hz or 60 Hz
(tolerance ± 0.25%).
1
Uninterruptible transfer: 0 ms
Interruptible transfer: ≤ 20 ms