Webui - Huawei UPS5000-E Series User Manual

Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(40 kVA-128 kVA)
User Manual (Integrated UPS 2.0)
Figure 6-38 Confirmation message
Step 4 Tap Yes. A message is displayed, indicating that the hibernation function is set successfully.
Step 5 Set the Module cycle hiber. period (d) parameter to an integer ranging from 1 to 100. The
default value is 30.
----End

6.13.2 WebUI

Procedure
Step 1 On the login page, enter a user name and password, and click Login to access the WebUI of
the UPS.
Step 2 Choose Monitoring > Param. Settings > Advanced Parameters, as shown in Figure 6-39.
Figure 6-39 Hibernation parameters on the WebUI
Step 3 On the WebUI, select Enable from the drop-down list box of a parameter and click Submit.
A message indicating that there is a risk is displayed. Click OK.
Issue 04 (2018-04-20)
Copyright © Huawei Technologies Co., Ltd.
6 Operations
187