UPS5000-E-(40 kVA-128 kVA)
User Manual (Integrated UPS 2.0)
Issue 04 (2018-04-20)
Installation time
A battery maintenance reminder is displayed when the maintenance time (counted from
the installation time) comes.
Maintenance period (d)
Interval for reminding users of battery maintenance.
Battery type
Set the battery type based on actual conditions. Currently, only lead-acid batteries are
supported.
Chg. cur. limiting coef. (C10)
Charging current limit, which is a multiple of the battery capacity. The value can be
0.05–0.15, 0.1 by default.
Cell float voltage (V/cell)
Set the float voltage. The value can be 2.23–2.27 V/cell, 2.25 V/cell by default. The
value is configurable in any mode.
Cell equalized volt. (V/cell)
Set the battery equalized voltage. The value can be 2.30–2.40 V/cell, 2.35 V/cell by
default. The value is configurable in any mode.
Transfer-to-equalized charging cur. Coef. (C10)
The battery enters equalized charge state when the battery current exceeds this parameter
value. The value range is 0.02–0.08, and the default value is 0.05.
Automatic equalized charging
When the value is Enable, the UPS automatically changes the battery management
status to equalized charging based on the charge current and float charge time.
Forced equalized charging protection time (h)
When batteries are continuously under float charging or hibernation, you can enable
forced equalized charging. When the forced equalized charging time reaches the value of
this parameter, float charging starts.
Equalized charging protection interval (d) and Scheduled equalized charging
interval (d)
After batteries transfer from equalized charging to float charging, if the batteries do not
discharge, equalized charging starts only after the float charging time reaches Equalized
charging protection interval. After equalized charging is complete, scheduled equalized
charging starts when the non-equalized charging time exceeds Scheduled equalized
charging interval.
Float volt. temp. comp.
Option to correct the float voltage based on the battery temperature when a battery
temperature sensor is connected. The value is configurable in any mode.
Float volt. temp. comp. coef. (mV/° C· cell)
Correction coefficient during float voltage temperature compensation.
Max. batt. dis. time (h)
Set the maximum battery discharge time. When the discharge time reaches the value, the
UPS powers off. The battery discharge time can be set only to 0 hours or a value in the
range 16–48 hours. The default value is 24 hours. If the time is set to 0 hours, battery
discharge protection is not implemented. This parameter cannot be set to a value in the
range 1–15 hours.
Sched. shallow dis. test