Figure 6-24 Setting ECO mode
Step 4 Manually start the inverter.
After the inverter starts, the UPS still works in bypass mode and the inverter is standby.
Figure 6-25 shows the power flow displayed on the System Status screen. If the bypass is
abnormal, the inverter supplies power immediately. If the inverter is not started, the UPS may
be disconnected.
Figure 6-25 System Status screen
----End
Issue 04 (2018-04-20)
Copyright © Huawei Technologies Co., Ltd.
6 Operations
176