Huawei UPS5000-E Series User Manual page 260

Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(40 kVA-128 kVA)
User Manual (Integrated UPS 2.0)
Alar
m
ID
(Ala
rm
ID-
Cau
se
ID)
0340
0345
0335
0594
-1
0095
-1
0096
-1
Issue 04 (2018-04-20)
Alarm
Sever
System Action
Name
ity
Maint.
Minor
None.
breaker
closed
Battery
Critic
None.
breaker
al
open
Genera
Warni
None.
tor
ng
connec
ted
Insuffi
Minor
This alarm does not
cient
trigger any action.
redund
ant
racks
Insuffi.
Minor
This alarm does not
redund
trigger any action.
ancy
1. The system
ECO
Minor
volt.
abnorm
al
2. If the system
Copyright © Huawei Technologies Co., Ltd.
Cause
Maint. breaker
closed
The battery
circuit breaker is
OFF.
Generator
connected
cannot transfer
to ECO bypass
mode.
works in ECO
bypass mode, it
transfers to
inverter or
bypass mode or
stops output.
Solution
Running status
displayed. No
suggested measures.
Running status
displayed. See
details about how to
handle other alarms.
Running status
displayed. No
suggested measures.
1. Reduce the load.
The load is
excessive.
2. Decrease the
configured
The
number of
configured
redundant racks.
number of
redundant
racks is
incorrect.
1. Reduce the load.
The load is
excessive.
2. Decrease the
configured
The
number of
configured
redundant
number of
modules.
redundant
modules is
incorrect.
1. Check the
The ECO
bypass input
bypass voltage
voltage and
or frequency is
frequency.
out of the
preset range.
2. Check that the
rated voltage,
The ECO
rated frequency,
bypass voltage
ECO bypass
or frequency
voltage range,
range is
and frequency
incorrectly set.
range are
The bypass
correctly set.
input sequence
3. Check that the
is reverse or
C Alarm List
252