Huawei UPS5000-E Series User Manual page 33

Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(40 kVA-128 kVA)
User Manual (Integrated UPS 2.0)
Silk
Screen
0V
GEN
0V
BCB_OL
BCB_STA
BCB_DR
V
BCB_0V
EPO_NO
EPO_12V
EPO_NC
EPO_12V
SWITCH
STATUS_
OUT
SWITCH
STATUS_
0V
SWITCH
STATUS_
MT
SWITCH
Issue 04 (2018-04-20)
Description
grounding faults
Port for signal ground
Port for detecting diesel
generator (D.G.) mode
Port for signal ground
Port for detecting the BCB
box
Port for monitoring the
battery switch
Controls battery circuit
breaker trip. When the
voltage is +12 V, the circuit
breaker trips.
Port for signal ground
Emergency power-off
(EPO) port
+12 V
EPO port
+12 V
Port for monitoring the UPS
output circuit breaker
Port for signal ground
Port for monitoring the
maintenance circuit breaker
Port for signal ground
Copyright © Huawei Technologies Co., Ltd.
Status
grounding fault
Disconnected: no
battery grounding
fault
Connected: D.G.
mode
Disconnected:
non-D.G. mode
Grounded: BCB
box connected
Disconnected:
BCB box not
connected
Connected: battery
switch ON
Disconnected:
battery switch
OFF
0 V: battery
switch not tripped
12 V: battery
switch tripped
If the normally open
(NO) port is
connected to the
EPO_12V port, EPO
is triggered.
If the normally closed
(NC) port is
disconnected from the
EPO_12V port, EPO
is triggered.
Connected: circuit
breaker ON
Disconnected:
circuit breaker
OFF
Disconnected:
circuit breaker ON
Connected: circuit
breaker OFF
2 Overview
Initial Status
Disconnected
Grounded
Disconnected
0 V
Disconnected
Connected
Connected
Disconnected
25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents