Procedure
The following steps are required to perform a firmware update:
● Click on "Browse" in the Firmware Loader area.
● Select the file you would like to use for the firmware update. You can find the available
firmware updates on the Service&Support page on the Internet
(http://support.automation.siemens.com).
Figure 3-31
● If the status is "Ready for update", click "Run update". If the CPU is in RUN mode during
the update, the following alarm is output:
Figure 3-32
Acknowledge the alarm output by clicking "OK". The CPU is set to STOP mode and the
firmware update is executed.

Web server

Function Manual, 11/2019, A5E03484625-AG
Status of the selected firmware file
Button to execute the update
Module information, "Firmware" tab, "Ready for update" status
Alarm after clicking "Run update"
Web pages
3.6 Firmware update
63