Web pages
3.16 User pages
Procedure
To define the user-defined pages in STEP 7 as the start page of the web server, proceed as
follows:
1. Select the CPU in the device configuration.
2. Open the settings in the Inspector window of the CPU under "Properties > General > Web
server".
3. Select the entry "AWP1" in the area "Entry page" under "Select entry page".
Figure 3-73
4. Download the configuration to the CPU.
If you now enter the IP address of the CPU in the browser, a connection is automatically
established to your user pages.
If you want to access the web pages of the CPU again, then link the web pages from your
user-defined pages e.g. via the URL "http://a.b.c.d./Portal/Portal.mwsl?PriNav=Start" or
"https://a.b.c.d/Portal/Portal.mwsl?PriNav=Start". The specification "a.b.c.d" is an example of
the IP address of the configured CPU.
Example of link in HTML:
<a href="/Portal/Portal.mwsl?PriNav=Start">SIMATIC web pages</a>
Note
If you define your user page as start page of the Web server, all direct access to the web
pages of the CPU is disabled. This applies also to the bookmarks you saved for the web
pages of the CPU as well as the page for reading out the service data.
Reading out service data
If you define your user page as start page of the Web server, all direct access to the web
pages for reading out the service data is also disabled.
If you want to continue to read out service data via the Web server when servicing is
required, here is how you can link the service data page directly to your user page.
Just as for the web pages of the CPU, link the service data page e.g. via the URL
"http://a.b.c.d/save_service_data" or "https://a.b.c.d/save_service_data", the "a.b.c.d" here is
an example of the IP address of the configured CPU.
Example of link in HTML:
<a href="/save_service_data">Service data</a>