Web Server Display And Operating Elements - Siemens Synco OZW772 Series Commissioning Instructions

Web server v6.0 for synco system
Hide thumbs Also See for Synco OZW772 Series:
Table of Contents

Advertisement

Overview
LED displays
1
(red/green/orange)
2
(green)
3 Field bus 2 (reserve)
4 Fault
(red)
5 Addressing mode (red)
Operating buttons
6 Remote button
7 Addressing mode
Button combinations
and
Switches
8
Message
suppression
9
DIP switch 2
Siemens
Building Technologies
1.2

Web Server display and operating elements

· Dark
No operating voltage DC 24 V
· Steady red
Web Server starts operating system
· Flashing red
Web Server starts application
· Steady green
Web Server operational, "Energy indicator" = "Green leaf"
· Steady orange
Web Server operational, "Energy indicator" = "Orange leaf"
· Flashing
Web Server operational, connected to portal
green / orange
(LED 0.8 s on, 0.2 s off)
· Dark
No bus power
· Lit
KNX operational
· Flashing
Communication on KNX
· Dark
No function
· Dark
No fault (normal operating state)
· Lit
Acknowledged fault
· Flashing
Unacknowledged fault
· Dark
KNX addressing mode off
· Lit
KNX addressing mode o
· Short (< 2 s)
Acknowledges fault message
· Long (> 6 s)
Sends system report to fault e-mail Receivers
(not to consumption data and "Energy indicator" Receivers)
· Short (< 2 s)
Press once: KNX addressing mode on
Press again: KNX addressing mode off
· Long (> 6 s)
Simultaneously pressing the buttons
defaults
device list, plant diagrams, and unsent messages are
deleted. History data is not deleted.
· Position ON
Sending messages is suppressed
· Position OFF
Sending messages permitted
· Switch settings No function
Web server OZW772... V6.0
Overview
All configuration data and settings are reset. The
Pos
Designation
1
LED
Operation, portal
connection display and "Energy
indicator"
2
LED
3
LED field bus 2 (reserve)
4
LED fault
5
LED addressing mode
6
Remote button
7
Addressing mode button
8
"Message suppression" switch
9
Switch 2 (no function)
10
KNX bus connection terminals
11
Operating voltage connection
12
USB connection Mini-B
13
Ethernet connection, RJ45 plug
and
restores
9 / 176
CE1C5701en
2015-10-12

Hide quick links: