 2-inch Pipe Mounting
Figure 3.4.4 2-inch Pipe Mounting
1. Pass the four clamp screws through the mounting
fixture.
2. position it on the 2-inch pipe, and then fasten the
AXG1A in place.
 Panel Mounting
Mounting fixture
Clamp screw
Figure 3.4.5 Panel Mounting
1. Fit the AXG1A into the panel.
2. Attach the mounting fixture to the AXG1A using the
screw and the washer, and secure the product with
the two clamp screws.

3.4.4 Mounting of AXFA11 Transmitter

AXFA11 Remote Transmitter can be mounted using
surface mounting, 2-inch pipe mounting, or panel
mounting, by the same process of AXG1A. Please refer
3.4.3. for the process.
IMPORTANT
Mounting fixture on equipment intended to be mounted
on a wall or ceiling shall withstand a force of four times
the weight of the equipment (AXFA11: 3.4 kg (7.5 lb)).
2-inch pipe
Mounting fixture
Washer
Clamp screw
F0328.ai
Unit: mm
(approx. inch)
Panel cutout
172 (6.8)
R3MAX
Washer
Screw
F0329.ai
<3. Installation>
3.5
Changing Direction of
Cable Entry
IMPORTANT
The following types can not be changed direction of
cable entry after delivery.
• Submersible Type (Suffix code: -W)
• For District Heating and Cooling or Condensation-
proof (Optional code: DHC)
(1) The following tool is required.
• Hexagonal wrench (nominal size 5)
(2) Turn off the power to the flowmeter.
(3) Using the wrench, unscrew the four hexagonal bolts
at the neck of transmitter or terminal box.
Transmitter
AXW Integral Flowmeter
CAUTION
Do not loosen the screw at the opposite side of cable
entry (see the figure below).
26
Terminal box
AXW Remote Sensor
F0330.ai
F0331.ai
IM 01E24A01-01EN