Parameter Setting From Display Panel - YOKOGAWA AXG1A Installation Manual

Magnetic flowmeter, size: 25 to 400 mm 1 to 16 in.
Hide thumbs Also See for AXG1A:
Table of Contents

Advertisement

5.4
Parameter Setting from
Display Panel
This section explains how to specify the parameters from
display panel. Select "Specialist" at the Operation Level
referring to Section 5.3. And select the parameters to be
specified in the Setting Mode.
When setting parameters on F
set appropriate MODE_BLK.Target on resource block,
transducer block or function block to "O/S". Parameter,
"All block target mode" can simplify the operation on
the display. By setting this parameter, resource block,
transducer block or function block can be set to O/S or
reset to the former setting at a time. The procedure to use
the parameter is as follows.
1. Set "O/S" on parameter "All block target mode".
2. Set the target parameter on display.
3. Set "Restore" on parameter "All block target mode".
Menu paths on display (there are 5 paths to reach):
Device setup ► Block mode ► All block target mode
Device setup ► Diag/service ► All block target mode
Device setup ► Wizard ► All block target mode
Device setup ► Detailed setup ► All block target mode
Device setup ► Detailed setup ► Fieldbus info ► All block target mode
NOTE
For the device with the ordering information specified at
ordering, the specified parameters (flow span and unit,
tag number, etc.) are stored in the device at the factory
shipment. Without the ordering information specified,
parameter setting needs to be done by user.
fieldbus type,
OUNDATION
<5. Basic Operating Procedures>
5.4.1 Setting example of Select type
Data: Flow rate unit
The following is the procedure of changing the flow
rate unit as Select type parameter according to the
specification of HART protocol.
The flow rate unit needs to be specified with "Physical
unit" and "Time unit" individually. When the flow rate unit
needs to be set "l/min", select "l (litter)" at the Physical unit
and "/min" at the Time unit.
Display Menu Path:
Device setup ► Detailed setup ► Pro var ► Volume ► Unit
Device setup ► Detailed setup ► Pro var ► Volume ► Time Unit
Specify the Physical unit for volumetric flow.
00 : 00
Volume
Move cursor with [INC] and [DEC] according
Damp pls/ttl
to the menu path above, and select the "unit"
Unit
then push [SET].
Time unit
SET
SFT
INC
F0519.ai
Move cursor with [INC] and [DEC], and
00 : 00
Unit
select the "l(liter)" then push [SET]. As the
m
3
selected unit is blinking, push [SET] to
l(liter)
determin. The screen returns to the setting
cm
3
page.
SET
SFT
INC
F0520.ai
Specify the Time unit for volumetric flow.
00 : 00
Volume
Move cursor with [INC] and [DEC] according
Unit
to the menu path above, and select the "Time
Time unit
unit" then push [SET].
Span
SET
SFT
INC
F0521.ai
Move cursor with [INC] and [DEC], and
00 : 00
Time unit
select the "/min" then push [SET]. As the
/s
selected unit is blinking, push [SET] to
/min
determin. The screen returns to the setting
/h
SET
SFT
INC
page after the setting.
F0522.ai
After completing the parameter setting, push
00 : 00
0.00000
PRV
[ESC] then the screen returns to the Display
l/min
Mode.
0.00000m/s
VEL
FLB
SET
SFT
INC
F0523.ai
NOTE
Be sure to set the Flow rate unit in the beginning when
the Flow rate unit and Flow span value are changed at
the same time.
When the unit is changed, the value of flow rate span is
converted to related values automatically according to
the unit change.
52
IM 01E24A01-01EN