54/91
Start-up
E1: Input terminal parameters
Code
E1.00 X1 input
E1.01 X2 input
E1.02 X3 input
E1.03 X4 input
E1.04 X5 input
E1.15 2-wire/3-wire control mode
E1.16 Digital input Up / Down change rate
Digital input Up / Down initial
E1.17
frequency
E1.25 Pulse input maximum frequency
E1.26 Pulse input filter time
E1.35 AI1 input mode
E1.40 AI2 input mode
E1.38 AI1 gain
E1.43 AI2 gain
E1.60 Motor temperature sensor channel
E1.61 Broken wire protection
E1.68 Analog input curve setting
E1.69 Analog input filter time
E1.70 Input curve 1 minimum
E1.71 Input curve 1 minimum frequency
E1.72 Input curve 1 maximum
E1.73 Input curve 1 maximum frequency
Bosch Rexroth AG R912005518_Edition 16
Name
0...51
0...4
0.10...100.00 Hz/s
0.00...[E0.09] Hz
0.0...50.0 kHz
0.000...2.000 s
0: 0...20 mA
1: 4...20 mA
2: 0...10 V
3: 0...5 V
4: 2...10 V
0.00...10.00
0.00...10.00
0: Inactive
1: AI1 analog input
2: AI2 analog input
3: EAI1 analog input
4: EAI2 analog input
5: TSI input (only for IO
plus card)
0: Inactive
1: Warning
2: Error
0...7
0.000...2.000 s
0.0 %...[E1.72]
0.00...[E0.09] Hz
[E1.70]...100.0 %
0.00...[E0.09] Hz
Rexroth Frequency Converter VFC
Setting range
Default
35
36
1.00
0.00
50.0
0.100
1.00
1.00
0.100
0.0
0.00
100.0
50.00
3610 / VFC 5610
Min.
Attri.
–
Stop
–
Stop
0
–
Stop
0
–
Stop
0
–
Stop
0
–
Stop
0.01
Run
0.01
Run
0.1
Run
0.001
Run
2
–
Run
1
–
Run
0.01
Run
0.01
Run
0
–
Stop
0
–
Stop
0
–
Run
0.001
Run
0.1
Run
0.01
Run
0.1
Run
0.01
Run