24/91
Electric Installation

Digital outputs

Terminal
Signal function
DO1a
Open collector output or
pulse output
DO1b
Ta
Relay changeover contacts
Tc
Tb
Relay shared contact

Analog outputs

Terminal
Signal function
AO1
Analog output
GND
Shared connection
Modbus communication
Terminal
Signal function
485+
Positive differential signal
485-
Negative differential signal
External control power supply
Terminal
Signal function
Auxiliary power supply
DC_IN
for control board
GND
Shared connection
Bosch Rexroth AG R912005518_Edition 16
Rexroth Frequency Converter VFC
Description
Open collector output:
See Group E2
Max. 30 VDC, 50 mA
COM is reference
Pulse output Max. frequency: 32.0 kHz
Rated capacity:
See Group E2
240 VAC, 3 A; 30 VDC, 3 A
Description
Voltage output: 0...10 V
Maximum load current for voltage out-
put: 5 mA
See Group E2
Current output: 0...20 mA
Maximum load resistance for current
output: 500 Ω
Isolated from COM
Description
GND is reference
Description
External +24 V supply input for con-
trol and panel boards
(NOT used for digital inputs)
Isolated from COM
3610 / VFC 5610
Signal requirement
Signal requirement
Signal requirement
Signal requirement
Rated capacity:
24 V (-10...+15 %)
200 mA