E8: Standard Communication Parameters - REXROTH VFC 3610 Quick Start Manual

Frequency converter
Hide thumbs Also See for VFC 3610:
Table of Contents

Advertisement

Rexroth Frequency Converter VFC
3610 / VFC 5610

E8: Standard communication parameters

Code
E8.00 Communication protocol
Communication error
E8.01
detection time
Communication error
E8.02
protection mode
Communication process data
E8.03
loss behavior
E8.10 Modbus baud rate
E8.11 Modbus data format
E8.12 Modbus local address
Modbus level / edge sensitivity
E8.13
selection
Setting range of E8.11:
0: N, 8, 1 (1 start bit, 8 data bits, 1 Stop bit, no parity)
1: E, 8, 1 (1 start bit, 8 data bits, 1 Stop bit, even parity)
2: O, 8, 1 (1 start bit, 8 data bits, 1 Stop bit, odd parity)
3: N, 8, 2 (1 start bit, 8 data bits, 2 Stop bits, no parity)
Name
0: Modbus
1: Extension card
0.0...60.0 s
(0.0: Inactive)
0: Freewheeling stop
1: Keep running
2: Emergency stop
0: Decelerating stop
1: Freewheeling stop
2: Keep running
3: Keep running without
warning
0: 1,200 bps
1: 2,400 bps
2: 4,800 bps
3: 9,600 bps
4: 19,200 bps
5: 38,400 bps
0...3
1...247
0: Level sensitive
1: Edge sensitive
Setting range
Default
R912005518_Edition 16 Bosch Rexroth AG
65/91
Start-up
Min.
Attri.
0
Stop
0.0
0.1
Stop
1
Stop
0
Stop
3
Stop
0
Stop
1
1
Stop
1
Stop