Rexroth Frequency Converter VFC
3610 / VFC 5610
Cable specification for USA / Canada
The data listed in the table below are only used to select fuse and
●
cable dimensions for USA / Canada.
Must use copper wires of 75 ℃ or above according to UL 508C.
●
It is recommended to use shielded cables to connect the motor.
●
*: If additional labels available with the terminals of 0K40...7K50,
●
please refer to the torque data on labels.
VFC x610
Fuse (Class J)
[A]
Model
0K40
10.0
0K75
15.0
1K50
25.0
2K20
30.0
Tab. 2-3: 1P 200 VAC fuse and cable dimensions for USA / Canada
VFC x610
Fuse (Class J)
[A]
Model
0K40
6.0
0K75
10.0
1K50
10.0
2K20
15.0
3K00
20.0
4K00
20.0
5K50
30.0
7K50
40.0
11K0
50.0
15K0
60.0
18K5
80.0
22K0
100.0
30K0
100.0
37K0
125.0
45K0
175.0
55K0
200.0
75K0
250.0
90K0
300.0
Power cables
[AWG]
14
14
10
10
Power cables
[AWG]
14
14
14
14
12
12
10
8
8
6
4
2
2
1
2 / 0
4 / 0
250 kcmil
350 kcmil
R912005518_Edition 16 Bosch Rexroth AG
Electric Installation
PE Cable
Torque / Screw
[AWG]
[N·m / lbf·in] (Mx)
8
0.8* / 7.0 (M3)
8
0.8* / 7.0 (M3)
8
0.8* / 7.0 (M3)
8
0.8* / 7.0 (M3)
PE Cable
Torque / Screw
[AWG]
[N·m / lbf·in] (Mx)
8
0.8* / 7.0 (M3)
8
0.8* / 7.0 (M3)
8
0.8* / 7.0 (M3)
8
0.8* / 7.0 (M3)
8
0.8* / 7.0 (M3)
8
0.8* / 7.0 (M3)
8
1.2* / 10.5 (M4)
8
1.2* / 10.5 (M4)
8
1.2 / 15.0 (M4)
6
1.2 / 15.0 (M4)
6
3.73 / 33.0 (M5)
4
3.73 / 33.0 (M5)
3
3.8 / 33.6 (M6)
3
3.8 / 33.6 (M6)
1 / 0
31.1 / 275.0 (5/16 in)
3 / 0
31.1 / 275.0 (5/16 in)
4 / 0
31.1 / 275.0 (5/16 in)
4 / 0
31.1 / 275.0 (5/16 in)
17/91