2.2 Cable Specifications

2.2.1 Power Connection

Cable specification for international without USA / Canada

Use copper wires specified for 90 ℃ or above.
Insulation based on IEC60364-5-52.
Cable with concentric shielding must be used.
According to IEC61800-5-1, PE cable must be at least 10 mm
double PE cable must be used.
*: If additional labels available with the terminals of 0K40...7K50,
please refer to the torque data on labels.
VFC x610
Fuse (gG)
Model
[A]
0K40
10.0
0K75
16.0
1K50
25.0
2K20
32.0
Tab. 2-1: 1P 200 VAC fuse and cable dimensions for international without USA / Canada
: Stranded with ferrule without plastic sleeve.
Fuse
VFC x610
(gG)
Model
[A]
0K40
6.0
0K75
10.0
1K50
10.0
Power cables installation mode
B1
B2
[mm
2
]
2.5
2.5
2.5
2.5
4.0
4.0
6.0
6.0
Power cables installation mode
B1
B2
[mm
2
]
2.5
2.5
2.5
2.5
2.5
2.5
PE Cable
E
[mm
2
]
10.0
2.5
2.5*2
10.0
2.5
2.5*2
10.0
2.5
4.0*2
10.0
4.0
6.0*2
PE Cable
E
[mm
2
]
10.0
2.5
2.5*2
10.0
2.5
2.5*2
10.0
2.5
2.5*2
R912005518_Edition 16 Bosch Rexroth AG
15/91
Electric Installation
2
or a
Torque / Screw
[N·m / lbf·in] (Mx)
0.8* / 7.0 (M3)
0.8* / 7.0 (M3)
0.8* / 7.0 (M3)
0.8* / 7.0 (M3)
Torque / Screw
[N·m / lbf·in] (Mx)
0.8* / 7.0 (M3)
0.8* / 7.0 (M3)
0.8* / 7.0 (M3)