Digital Output Do1A, Do1B Load Pull-Up / Pull-Down Wiring - REXROTH VFC 3610 Quick Start Manual

Frequency converter
Hide thumbs Also See for VFC 3610:
Table of Contents

Advertisement

26/91
Electric Installation

Digital output DO1a, DO1b load pull-up / pull-down wiring

Load pull-up wiring with internal power
supply
Load pull-down wiring with internal
power supply
Fig. 2-7: Digital output DO1a, DO1b load pull-up / pull-down wiring
For internal supply, ONLY USE terminal +24 V and NEVER USE terminal +10 V
or +5 V!
For external supply, its reference ground MUST be connected to terminal
COM!
Bosch Rexroth AG R912005518_Edition 16
Rexroth Frequency Converter VFC
Load pull-up wiring with external power
supply
Load pull-down wiring with external
power supply
3610 / VFC 5610