26/91
Electric Installation
Digital output DO1a, DO1b load pull-up / pull-down wiring
①
Load pull-up wiring with internal power
supply
②
Load pull-down wiring with internal
power supply
Fig. 2-7: Digital output DO1a, DO1b load pull-up / pull-down wiring
For internal supply, ONLY USE terminal +24 V and NEVER USE terminal +10 V
●
or +5 V!
For external supply, its reference ground MUST be connected to terminal
●
COM!
Bosch Rexroth AG R912005518_Edition 16
Rexroth Frequency Converter VFC
③
Load pull-up wiring with external power
supply
④
Load pull-down wiring with external
power supply
3610 / VFC 5610