Bosch Rexroth AG
Electric Installation
Cable specification for USA / Canada
ONLY USE copper wires of 75 ℃ or above according to UL 508C.
●
It is recommended to use shielded cables to connect the motor.
●
Model 3K00: ONLY available with VFC 3610.
●
*: If additional labels available with the terminals of 0K40...7K50,
●
please refer to the torque data on labels.
VFC x610
Fuse (gG)
[A]
Model
0K40
10.0
0K75
15.0
1K50
25.0
2K20
30.0
Tab. 2-3: 1P 200 VAC fuse and cable dimensions for USA / Canada
VFC x610
Fuse (gG)
[A]
Model
0K40
6
0K75
10
1K50
10
2K20
15
3K00
20
4K00
20
5K50
30
7K50
40
11K0
50
15K0
60
18K5
80
Tab. 2-4: 3P 400 VAC fuse and cable dimensions for USA / Canada
8/51
Power cables
[AWG]
14
14
10
10
Power cables
[AWG]
14
14
14
14
12
12
10
8
8
6
4
VFC 3610 / VFC 5610
PE Cable
Torque / Screw
[AWG]
[N·m / lb·in] (Mx)
14
1.00* / 9.0 (M3)
14
1.00* / 9.0 (M3)
10
1.00* / 9.0 (M3)
10
1.00* / 9.0 (M3)
PE Cable
Torque / Screw
[AWG]
[N·m / lb·in] (Mx)
14
1.00* / 9.0 (M3)
14
1.00* / 9.0 (M3)
14
1.00* / 9.0 (M3)
14
1.00* / 9.0 (M3)
12
1.00* / 9.0 (M3)
12
1.00* / 9.0 (M3)
10
1.20* / 10.5 (M4)
8
1.20* / 10.5 (M4)
8
1.76 / 15.6 (M4)
6
1.76 / 15.6 (M4)
6
3.73 / 33.0 (M5)
DOK-RCON04-VFC-X610***-QU06-EN-P