Points List In Description Order - Johnson Controls Simplicity LINC Application Manual

Table of Contents

Advertisement

1031990-UAD-A-0313
TABLE 2: POINTS LIST IN DESCRIPTION ORDER
BACnet
BACnet
Read/
Object
Object
Write
Type
Inst
R / W
(5) BV
109
R / W
(5) BV
101
R / W
(5) BV
100
R / W
(5) BV
99
R / W
(5) BV
108
R / W
(2) AV
14
R
(2) AI
15
R
(2) AI
86
R
(5) BI
16
R / W
(2) AV
79
R
(5) BI
85
R
(5) BI
86
R
(5) BI
87
R
(5) BI
88
R
(5) BI
89
R
(2) AI
33
R / W
(5) BV
29
R / W
(2) AV
57
R / W
(2) AV
25
R / W
(5) BV
34
R / W
(5) BV
35
R
(5) BI
33
R / W
(2) AV
24
R / W
(5) BV
23
R
(2) AI
56
R / W
(5) BV
21
R / W
(2) AV
8
4
Descriptor
COMM_IAQ
COMM_OAT
COMM_OH
COMM_RH
COMM_ST
ACC_OVER_TME
ACTIVE_ALARM
AIR_MON_INPUT
AIR_PROOF_SW
OAQ_STPT
ALARM_1_ON
ALARM_2_ON
ALARM_3_ON
ALARM_4_ON
ALARM_5_ON
BLDG_STATIC
BP_SENS_INST
BLDG_SP_STPT
COM_V_LOW_SP
CVM_COOLING
CVM_HEATING
COM_VENT_STA
COM_V_HI_SP
COOLING_ENA
CV_VAV_SELEC
FAN_ON_W_SEN
IAQ_VALUE
Default Min Max Point Description
Accept Comm Value for Indoor Quality
n/a
n/a
n/a
Sensor
n/a
n/a
n/a
Accept Comm Value for OAT
n/a
n/a
n/a
Accept Comm Value for OH
n/a
n/a
n/a
Accept Comm Value for RH
Accept Comm Value for Space
n/a
n/a
n/a
Temperature
Accumulated Unoccupied Override
n/a
n/a
n/a
Time (in hours)
n/a
n/a
n/a
Active Alarm
0
0
10
Air Monitor Station Input
Air Proving Switch Status (1=closed,
n/a
n/a
n/a
0=open / no air flow)
1000
0
5000
Air Quality Setpoint Outside
Alarm Buffer #1 (0=Alarm has cleared,
n/a
n/a
n/a
1=Alarm is still active)
Alarm Buffer #2 (0=Alarm has cleared,
n/a
n/a
n/a
1=Alarm is still active)
Alarm Buffer #3 (0=Alarm has cleared,
n/a
n/a
n/a
1=Alarm is still active)
Alarm Buffer #4 (0=Alarm has cleared,
n/a
n/a
n/a
1=Alarm is still active)
Alarm Buffer #5 (0=Alarm has cleared,
n/a
n/a
n/a
1=Alarm is still active)
n/a
n/a
n/a
Building Static Pressure
Building Static Pressure Sensor
n/a
n/a
n/a
Installed
0.15
-0.25 0.25
Building Static Pressure Setpoint
Comfort Ventilation LowerSetpoint
70
60
80
(degrees F)
Comfort Ventilation Mode for Cooling
n/a
n/a
n/a
Enabled
Comfort Ventilation Mode for Heating
n/a
n/a
n/a
Enabled
Comfort Ventilation Mode Status
n/a
n/a
n/a
(1=control is in Comfort Vent mode, 0= it
is not)
Comfort Ventilation Upper Setpoint
80
65
85
(degrees F)
n/a
n/a
n/a
Cooling Mode Enabled
CV / VAV Selected (0= Valid CV,
n/a
n/a
n/a
1=Valid VAV, 2= Invalid Value)
CV-Indoor Fan Operates with Space
n/a
n/a
n/a
Sensor Present Option Enabled
n/a
0
5000
Demand Ventilation (IAQ) Value (PPM)
Johnson Controls Unitary Products

Hide quick links: