TABLE 3: POINTS LIST IN OBJECT ORDER
BACnet
BACnet
Read/
Object
Object
Write
Type
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R
(2) AI
R
(2) AI
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R
(2) AI
R / W
(2) AV
R
(2) AI
R / W
(2) AV
R
(2) AI
R / W
(2) AV
R
(2) AI
R
(2) AI
R
(2) AI
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
12
Descriptor
Inst
1
OCC_COOL_SP
2
UNOC_COOL_SP
3
SAT_COOL_SP
4
SUP_AIR_TEMP
5
RET_AIR_TEMP
6
SPACE_TEMP
7
AMB_TEMP
8
IAQ_VALUE
9
OAQ_VALUE
10
AMB_AIR_HUM
11
AMB_AIR_ENTH
12
RET_AIR_HUM
13
RET_AIR_ENTH
14
ACC_OVER_TME
15
ACTIVE_ALARM
16
NUMBER_COMPS
17
OP_COOL_STPT
18
DEMVENT_STPT
19
ECON_MIN_POS
20
ECO_1ST_STPT
21
ECO_2ND_STPT
22
ECON_OAEN_SP
23
ECON_OAT_ENA
24
COM_V_HI_SP
25
COM_V_LOW_SP
26
TEM_HUM_STPT
27
HGR_HUM_STPT
28
MAX_TH_OFSET
Default
Min
Max
72
46
99
85
46
99
50
40
65
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
0
5000
n/a
0
5000
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
2
4
n/a
n/a
n/a
1000
0
5000
20
0
100
55
40
65
50
40
65
27
10
50
55
40
80
80
65
85
70
60
80
50
20
80
50
0
100
3
0
5
Point Description
Occupied Cooling Setpoint
Un-Occupied Cooling Setpoint
Supply Air Temperature Limit for
Cooling Setpoint (degrees F)
Supply Air Temperature
Return Air Temperature
Space (Indoor) Air Temperature
Outside Air Temperature
Demand Ventilation (IAQ) Value (PPM)
Outside Demand Ventilation (OAQ)
Value (PPM)
Outside Air Humidity
Outside Air Enthalpy
Return Air Humidity
Return Air Enthalpy
Accumulated Unoccupied Override
Time (in hours)
Active Alarm
Number of Compressors Available
Operating Cooling Setpoint
Demand Ventilation Setpoint
Economizer Minimum Position
Economizer First Stage Setpoint
Economizer Second Stage Setpoint
Economizer Outside Air Enthalpy
Setpoint
Economizer Outside Air Temperature
Enable Setpoint
Comfort Ventilation Upper Setpoint
(degrees F)
Comfort Ventilation LowerSetpoint
(degrees F)
Temperature / Humidity Setpoint
(percent Humidity)
Hot Gas Reheat Humidity Setpoint
(percent Humidity)
Max Temperature / Humidity Setpoint
Offset
Johnson Controls Unitary Products