1031990-UAD-A-0313
TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
BACnet
BACnet
Read/
Object
Object
Write
Type
R / W
(2) AV
R
(2) AI
R
(2) AI
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R
(2) AI
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R / W
(2) AV
R
(2) AI
14
Descriptor
Inst
54
OAT_HEAT_L_O
55
HW_VLV_OUT
56
CV_VAV_SELEC
57
BLDG_SP_STPT
58
DUCT_SP_STPT
59
DUCT_SD_STPT
60
VAV_OHEAT_SP
61
MWU_RAT_STPT
62
HYD_S1_SA_SP
63
HYD_S2_SA_SP
64
VAV_CL_HI_SP
65
VAV_CL_LO_SP
66
VAV_SAT_RSET
67
REVISION
69
OP_STPT_DIF
70
SAT_ALM_COOL
71
SPCE_ALM_TMP
72
SPCE_ALM_TIM
73
SP_OFF_RANGE
74
OAT_COOL_L_O
75
UNOC_OVR_TP
76
H1_ACCUM_HRS
Default
Min
Max
75
0
100
n/a
n/a
n/a
n/a
n/a
n/a
0.15
-0.25
0.25
1.5
0
5
4.5
0
5
68
40
85
70
50
85
120
80
180
150
81
180
60
41
70
55
40
69
72
40
85
n/a
n/a
xx
1
1
5
0
0
80
0
0
25
0
0
120
3
0
5
45
0
100
60
0
240
n/a
n/a
n/a
Point Description
Outdoor Air Temperature
HeatingLockout Temperature
Hot Water Valve Output Status (0-
100%)
CV / VAV Selected (0= Valid CV,
1=Valid VAV, 2= Invalid Value)
Building Static Pressure Setpoint
Duct Static Pressure Setpoint
Duct Static Pressure Shutdown
Setpoint
VAV Occupied Heating Setpoint
(degrees F)
Morning Warm-Up and VAV Heating:
Return Air Temperature Setpoint
(degrees F)
Hydronic Heating Stage #1 Supply Air
Setpoint (degrees F)
Hydronic Heating Stage #2 Supply Air
Setpoint (degrees F)
VAV Cooling Supply Air Temperature:
Upper Setpoint (degrees F)
VAV Cooling Supply Air Temperature:
Lower Setpoint (degrees F)
VAV Cooling Supply Air Temperature:
Reset Setpoint (Space
Temperature)(degrees F)
Device Revision
Operating Setpoint Differential
Supply Air Temperature Alarm
Setpoint for Cooling
Space Sensor Alarm Temperature
(degrees F, 0 = disabled)
Space Sensor Alarm Time (minutes F,
0 = disabled)
Space Temprature Sensor Offset
Range (0-5 degrees)
Outdoor Air Temperature Cooling
Lockout Temperature
Unoccupied Override Time Period
Heating #1 Accumulated Run Time (in
hours)
Johnson Controls Unitary Products
Need help?
Do you have a question about the Simplicity LINC and is the answer not in the manual?