1031990-UAD-A-0313
TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
BACnet
BACnet
Read/
Object
Object
Write
Type
R / W
(5) BV
R / W
(5) BV
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
R / W
(5) BV
R / W
(5) BV
R / W
(5) BV
R / W
(5) BV
R / W
(5) BV
R / W
(5) BV
R / W
(5) BV
R / W
(5) BV
R / W
(5) BV
R / W
(5) BV
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
16
Descriptor
Inst
12
REDLINE
13
LOADSHED
14
LOW_SUP_VOLT
15
DIRT_FILT_SW
16
AIR_PROOF_SW
17
PURGE_SWITCH
18
HGR_STAT
19
LOW_AMB_OVRD
20
POP_ENABLED
21
FAN_ON_W_SEN
22
SAT_COOLING
23
COOLING_ENA
24
SAT_HEATING
25
HEATING_ENA
26
SEN_FAULT_EN
28
INTELLI-STRT
29
BP_SENS_INST
30
EX_FAN_STAT
31
ECONO_STATUS
32
FRECOOL_STAT
33
COM_VENT_STA
Default
Min
Max
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Point Description
Redline (0=clear redline, 1=set redline
operation)
Loadshed (0=clear loadshed, 1=set
loadshed operation)
Low Supply Voltage (0=comps not
overridden by LSV, 1=comps
overridden)
Dirty Filter Switch Status
(0=open,1=closed / fault)
Air Proving Switch Status (1=closed,
0=open / no air flow)
Purge Switch Status
(0=open,1=closed)
Hot Gas Reheat Output Status
(0=output is OFF, 1=output is ON)
Low Ambient Temperature (0=comps
not overridden by LAT, 1=comps
overridden)
Pre-Occupancy Purge Enabled
CV-Indoor Fan Operates with Space
Sensor Present Option Enabled
Supply Air Temperature Limit for
Cooling Enabled
Cooling Mode Enabled
Supply Air Temperature Limit for
Heating Enabled
Heating Mode Enabled
Space Sensor Fault Override
(Construction Mode) Enabled
Intelli-Start Enabled
Building Static Pressure Sensor
Installed
Exhaust Fan Output Status (0=output
is OFF, 1=output is ON)
Economizer Output Status (0=not Free
Cooling, 1= Free Cooling)
Free Cooling Mode Status (0=comps
not overridden by Econo, 1=comps
overridden)
Comfort Ventilation Mode Status
(1=control is in Comfort Vent mode, 0=
it is not)