OVERVIEW

®
The Simplicity
LINC Gateway operates as a Modbus® Client
providing an interface between a BACnet® MS/TP control system
and devices that communicate using the Modbus RTU protocol.
®
The Simplicity
LINC allows monitoring and control by a third-party
BACnet Building Automation System (BAS).
®
The Simplicity
LINC is preconfigured to provide an interface to UP
products equipped with Simplicity
4/2/2008 as well as prior Simplicity
Intelli-Comfort™ controllers.
R
C
24 — must be grounded
close to the
24V power is polarity sensitive, incorrect
wiring could result in board damage.
FIGURE 1: WIRE CONNECTIONS
APPLICATION GUIDE
Simplicity
®
controllers manufactured after
®
Elite™ and Simplicity
®
LINC
®
LINC GATEWAY
ConFig v1.01d
The Simplicity
unit and utilizes 24 VAC power from the unit's control transformer.
One port is connected to the UP controller. The other port must be
connected to the BACnet MS/TP network.
The Simplicity
operational data points from the controller and expose them on a
BACnet MS/TP network.
NOTE: Not all Simplicity
monitored by the Simplicity
®
with
®
LINC mounts inside the control panel of the UP
®
LINC Gateway is preconfigured to obtain
®
operating parameters are controlled/
®
LINC.
The shield must be
connected to ground at
each device.
1031990-UAD-A-0313

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Simplicity LINC and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Johnson Controls Simplicity LINC

  • Page 1 APPLICATION GUIDE ® Simplicity LINC GATEWAY ConFig v1.01d ® OVERVIEW The Simplicity LINC mounts inside the control panel of the UP unit and utilizes 24 VAC power from the unit’s control transformer. ® One port is connected to the UP controller. The other port must be The Simplicity LINC Gateway operates as a Modbus®...
  • Page 2 DIP switch setting creates a default DE of 23001. 57600 The default Unit Name is YORK_RTU. 76800 115200 MAC Address of 21 Baud Rate of 38400 MAC Address of 99 FIGURE 2: MAC ADDRESS EXAMPLES Johnson Controls Unitary Products...
  • Page 3 SOURCE1 (Toll-free at 1-800-536-6112). found to comply with all the SOFTWARE SETUP necessary interoperability requirements. ® The control sequence is managed by the Simplicity controller. The data points on these systems are mapped to standard Johnson Controls Unitary Products...
  • Page 4 CV / VAV Selected (0= Valid CV, (2) AI CV_VAV_SELEC 1=Valid VAV, 2= Invalid Value) CV-Indoor Fan Operates with Space R / W (5) BV FAN_ON_W_SEN Sensor Present Option Enabled R / W (2) AV IAQ_VALUE 5000 Demand Ventilation (IAQ) Value (PPM) Johnson Controls Unitary Products...
  • Page 5 Elite Compressor #2 Overload Switch (5) BI E_C2_OVRLOAD Input Status (1=closed, 0=open / fault) Elite Compressor #3 Accumulated Run (2) AI E_C3_ACM_HRS Time (in hours) Elite Compressor #3 Output Status (5) BI E_COMP3_STAT (0=output is OFF, 1=output is ON) Johnson Controls Unitary Products...
  • Page 6 E_LIMIT_ 2 (1=closed, 0=open / fault) Elite Limit Switch #3 Input Status (5) BI E_LIMIT_ 3 (1=closed, 0=open / fault) Elite Low Pressure Switch for (5) BI E_LPS1 Compressor #1 Input Status (1=closed, 0=open / fault) Johnson Controls Unitary Products...
  • Page 7 R / W (5) BV HEATING_ENA Heating Mode Enabled Hot Gas Reheat Humidity Setpoint R / W (2) AV HGR_HUM_STPT (percent Humidity) Hot Gas Reheat Output Status (5) BI HGR_STAT (0=output is OFF, 1=output is ON) Johnson Controls Unitary Products...
  • Page 8 Compressor #1 Input Status (1=closed, 0=open / fault) Intelli-Comfort High Pressure Switch for (5) BI I_HPS2 Compressor #2 Input Status (1=closed, 0=open / fault) Intelli-Comfort Indoor Fan Output Status (5) BI I_IFAN_STAT (0=output is OFF, 1=output is ON) Johnson Controls Unitary Products...
  • Page 9 Occupied Heating Setpoint R / W (5) BV OCCUPIED_ENA Occupied Input Enabled Occupied Thermostat or R / W (5) BV OCC_COMS_ENA Communication Input Enabled (2) AI OP_COOL_STPT Operating Cooling Setpoint (2) AI OP_HEAT_STPT Operating Heating Setpoint Johnson Controls Unitary Products...
  • Page 10 R / W (2) AV SAT_ALM_HEAT for Heating Supply Air Temperature Limit for R / W (5) BV SAT_COOLING Cooling Enabled Supply Air Temperature Limit for R / W (2) AV SAT_COOL_SP Cooling Setpoint (degrees F) Johnson Controls Unitary Products...
  • Page 11 Upper Setpoint (degrees F) R / W (5) BV VAV_OCC_HEAT VAV Occupied Heating Enabled VAV Occupied Heating Setpoint R / W (2) AV VAV_OHEAT_SP (degrees F) R / W (5) BV VAV_UNOCC_HEAT VAV Unoccupied Heating Enabled Johnson Controls Unitary Products...
  • Page 12 Temperature / Humidity Setpoint R / W (2) AV TEM_HUM_STPT (percent Humidity) Hot Gas Reheat Humidity Setpoint R / W (2) AV HGR_HUM_STPT (percent Humidity) Max Temperature / Humidity Setpoint R / W (2) AV MAX_TH_OFSET Offset Johnson Controls Unitary Products...
  • Page 13 R / W (2) AV UNOC_HEAT_SP Un-Occupied Heating Setpoint R / W (2) AV SAT_HEAT_SP Supply Air Temperature Limit for Heating Setpoint (degrees F) R / W (2) AV SAT_ALM_HEAT Supply Air Temperature Alarm Setpoint for Heating Johnson Controls Unitary Products...
  • Page 14 Space Temprature Sensor Offset Range (0-5 degrees) R / W OAT_COOL_L_O Outdoor Air Temperature Cooling (2) AV Lockout Temperature R / W (2) AV UNOC_OVR_TP Unoccupied Override Time Period H1_ACCUM_HRS Heating #1 Accumulated Run Time (in (2) AI hours) Johnson Controls Unitary Products...
  • Page 15 ECONO_INST Economizer Installed R / W (5) BV PWR_EX_INST Power Exhaust Installed R / W (5) BV MOD_EX_INST Modulating Exhaust Installed R / W (5) BV EX_VFD_INST Exhaust VFD Installed (5) BI MODBUS_ALARM Modbus Communication Alarm Johnson Controls Unitary Products...
  • Page 16 Economizer Output Status (0=not Free Cooling, 1= Free Cooling) (5) BI FRECOOL_STAT Free Cooling Mode Status (0=comps not overridden by Econo, 1=comps overridden) (5) BI COM_VENT_STA Comfort Ventilation Mode Status (1=control is in Comfort Vent mode, 0= it is not) Johnson Controls Unitary Products...
  • Page 17 (0=output is OFF, 1=output is ON) (5) BI E_COMP3_STAT Elite Compressor #3 Output Status (0=output is OFF, 1=output is ON) (5) BI E_LPS3 Elite Low Pressure Switch for Compressor #3 Input Status (1=closed, 0=open / fault) Johnson Controls Unitary Products...
  • Page 18 H1 Heating Output #1 Status (0=output is OFF, 1=output is ON) (5) BI HEAT_2_STAT H2 Heating Output #2 Status (0=output is OFF, 1=output is ON) (5) BI HEAT_3_STAT H3 Heating Output #3 Status (0=output is OFF, 1=output is ON) Johnson Controls Unitary Products...
  • Page 19 Alarm Buffer #2 (0=Alarm has cleared, 1=Alarm is still active) (5) BI ALARM_3_ON Alarm Buffer #3 (0=Alarm has cleared, 1=Alarm is still active) (5) BI ALARM_4_ON Alarm Buffer #4 (0=Alarm has cleared, 1=Alarm is still active) Johnson Controls Unitary Products...
  • Page 20 R / W (5) BV COMM_IAQ Accept Comm Value for Indoor Quality Sensor R / W (5) BV MIN_AMB_SEN Minimum Outdoor Air Sensor Enabled R / W (5) BV REM_CONT_BAS_ECO Remote Control Third Party BAS Economizer Enable Johnson Controls Unitary Products...
  • Page 21: Troubleshooting

    15 seconds after powering up the 4 unused LEDs will turn on solid for 5 seconds, then turn off. On normal operation of Simplicity Linc, the RX LED will flash when a message is received on the field port. On normal operation of Simplicity Linc, the TX LED will flash when a message is sent on the field port.
  • Page 22 ® FIGURE 3: SIMPLICITY LINC BOARD AND LED LAYOUT Subject to change without notice. Printed in U.S.A. 1031990-UAD-A-0313 Copyright © 2013 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing Johnson Controls Unitary Products 5005 York Drive Norman, OK 73069...