Johnson Controls Simplicity LINC Application Manual page 19

Table of Contents

Advertisement

TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
BACnet
BACnet
Read/
Object
Object
Write
Type
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
R
(5) BI
Johnson Controls Unitary Products
Descriptor
Inst
71
I_IFAN_STAT
72
I_FAN_OVER
73
I_COMP1_STAT
74
I_LPS1
75
I_HPS1
76
I_COMP2_STAT
77
I_LPS2
78
I_HPS2
79
I_CFAN_STAT
80
I_GAS_VLVE1
81
I_LIMIT_1
82
I_FREEZE_1
83
I_FREEZE_2
85
ALARM_1_ON
86
ALARM_2_ON
87
ALARM_3_ON
88
ALARM_4_ON
Default
Min
Max
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
1031990-UAD-A-0313
Point Description
Intelli-Comfort Indoor Fan Output
Status (0=output is OFF, 1=output is
ON)
Intelli-Comfort Fan Overload Switch
Input Status (0=open,1=closed)
Intelli-Comfort Compressor #1 Input
Status (0=output is OFF, 1=output is
ON)
Intelli-Comfort Low Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open / fault)
Intelli-Comfort High Pressure Switch
for Compressor #1 Input Status
(1=closed, 0=open / fault)
Intelli-Comfort Compressor #2 Input
Status (0=output is OFF, 1=output is
ON)
Intelli-Comfort Low Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open / fault)
Intelli-Comfort High Pressure Switch
for Compressor #2 Input Status
(1=closed, 0=open / fault)
Intelli-Comfort Condenser Fan #1 Input
Status (0=output is OFF, 1=output is
ON)
Intelli-Comfort Gas Valve #1 Input
Status
Intelli-Comfort Limit Switch #1 Input
Status
Intelli-Comfort Freeze Thermostat
Switch #1 Input Status
(0=open,1=closed)
Intelli-Comfort Freeze Thermostat
Switch #2 Input Status
(0=open,1=closed)
Alarm Buffer #1 (0=Alarm has cleared,
1=Alarm is still active)
Alarm Buffer #2 (0=Alarm has cleared,
1=Alarm is still active)
Alarm Buffer #3 (0=Alarm has cleared,
1=Alarm is still active)
Alarm Buffer #4 (0=Alarm has cleared,
1=Alarm is still active)
19