Technical Data - Beckhoff EL6751 Documentation

Master/slave terminal for canopen
Table of Contents

Advertisement

2.2

Technical data

Technical data
Bus system
Version
Number of fieldbus channels
Data transfer rate
Bus interface
Bus devices
Communication
Diagnostics
Power supply
Current consumption via E-bus
Electrical isolation
Configuration
Weight
Permissible ambient temperature range
during operation
Permissible ambient temperature range
during storage
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 18]
Vibration/shock resistance
EMC immunity/emission
Protection class
Installation position
Approval
EL6751
EL6751-0000
CANopen
Master
1
10, 20, 50, 100, 125, 250, 500, 800 or 1000 kbaud
D-Sub 9-pole connector according to CANopen specification,
galvanically uncoupled
maximum 127 slaves
CANopen network master and
CANopen manager
Status LEDs
via the E-bus
typ. 230 mA
500 V (E-bus/CANopen)
with TwinCAT System Manager
approx. 70 g
-25 °C ... +60 °C (extended temperature range)
-40 °C ... +85 °C
95 %, no condensation
approx. 26 mm x 100 mm x 52 mm (width aligned: 23 mm)
on 35 mm mounting rail conforms to EN 60715
conforms to EN 60068-2-6 / EN 60068-2-27
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE
ATEX [} 25]
cULus [} 26]
Version: 3.5
Product overview
EL6751-0010
Slave
CANopen slave
15