To Wire The Wireless Adapter For Wireless Sensors - Carrier MPC Open XP Series Installation And Startup Manual

Table of Contents

Advertisement

2
Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation.
Strip about .25 inch (.6 cm) of the inner insulation from each wire.
.25 in.
(.6 cm)
3
Wire each terminal on the sensor to the same terminal on the controller. See diagram below.
NOTE Carrier recommends that you use the following Rnet wiring scheme:
Connect this wire...
Red
Black
White
Green
4
Apply power to the MPC Open XP.

To wire the Wireless Adapter for wireless sensors

WARNING Do not apply line voltage (mains voltage) to the Wireless Adapter.
The Carrier wireless sensors are available in 868, 902, and 928 MHz radio frequency. The sensors are thermistor-
based temperature sensors that may optionally sense humidity.
Wireless sensors communicate through a Wireless Adapter, which is wired to the Rnet port of the controller.
REQUIREMENTS
A v6.5 or later i-Vu® system
v6-xx-xxx or later controller drivers
To configure the control program for the desired user interaction with the sensor, see the Wireless Sensors
Application Guide. For detailed instructions, see the Wireless Sensors Installation Guide.
MPC Open XP
MPC Open XPIO48/816
Installation and Start-up Guide
Outer Jacket
Inner insulation
To this terminal...
+12V
Rnet-
Rnet+
Gnd
21
Installing the MPC Open XP
CARRIER CORPORATION ©2019