Input wiring specifications

Input
0–5 Vdc
0–10 Vdc
0–20 mA
Thermistor
Dry contact
Pulse counter
TLO
RTD
ZS sensors
Wireless Adapter for
Wireless sensors
Equipment Touch
TruVu™ ET Display

Outputs

The MPC Open XP and expanders have universal outputs that you can use as binary outputs or analog outputs.
The outputs support:
driving external 24 Vdc relays
0-10 Vdc devices
0-20 mA devices
WARNING Binary outputs are powered, 24 Vdc channels. Dry contact binary outputs are not supported in
this product line. Do NOT apply 24 Vac to these universal outputs.
If output controls a...
0–10 Vdc device
0–20 mA device
NOTES
The device must share the same ground as the controller.
The total output current from all outputs and the Aux Power Out connection must not exceed:
500 mA at 115°F
300 mA at 140°F
For temperatures above 115°F, use the following equation to calculate the total current at 8 mA per degree:
MPC Open XP
MPC Open XPIO48/816
Installation and Start-up Guide
Maximum length
500 feet
(152 meters)
1000 feet
(305 meters)
500 feet
(152 meters)
100 feet
(30 meters)
See Wiring devices to the MPC Open XP's Rnet port (page 19).
Resistance to ground must be...
500 Ohms minimum
800 Ohms maximum
15
Minimum gauge
Shielding
22 AWG
100 feet Unshielded
100 - 500 feet Shielded
22 AWG
100 feet Unshielded
100 - 1000 feet Shielded
22 AWG
100 feet Unshielded
100 - 500 feet Shielded
22 AWG
Shielded
Installing the MPC Open XP