Freely Assignable Digital Outputs (Digout) - Lenze 9300 Series System Manual

Servo position controllers
Hide thumbs Also See for 9300 Series:
Table of Contents

Advertisement

Function library
Function blocks
3.5.33

Freely assignable digital outputs (DIGOUT)

3.5.33
Freely assignable digital outputs (DIGOUT)
Purpose
Conditioning of the digital signals and output at the terminals X5/A1 to X5/A4.
Fig. 3−136
Freely assignable digital outputs (DIGOUT)
Name
DIGOUT1
DIGOUT2
DIGOUT3
DIGOUT4
Function
The terminals X5/A1 to X5/A4 are updated every millisecond. The level for every output can be
inverted. For this, proceed as follows:
l
Select code C0118 with corresponding subcode (e.g. subcode 3 for output X5/A3)
l
Enter the desired level as a parameter:
– 0 = Level not inverted (HIGH active)
– 1 = Level inverted (LOW active)
3−186
C0117/1
C0117/2
C0117/3
C0117/4
Signal
Type
DIS
DIS format
d
C0444/1
bin
d
C0444/2
bin
d
C0444/3
bin
d
C0444/4
bin
EDSVS9332P−EXT DE 2.0
DIGOUT
DIGOUT1
X5
C0118/1...4
DIGOUT2
A1
DIGOUT3
0
DIGOUT4
A2
1
1
C0444/1
A3
C0444/2
C0444/3
A4
C0444/4
Source
CFG
List
Lenze
C0117/1
2
15000
C0117/2
2
10650
C0117/3
2
500
C0117/4
2
5003
Note