User Interface; Zone Options; Output Options; Mains Power - Siemens FC121-ZA Technical Manual

Fire control panel
Hide thumbs Also See for FC121-ZA:
Table of Contents

Advertisement

7.2.4
Lamp test available at
User
access level 2
interface
Silence key with
EVAC function
Silence on ACK
ACK available at
access level 1
LED fire brigade
activated by alarm
dialer output
LED fire brigade
activated via input
Display view
7.2.5
Zone
Device coincidence
options
inhibit time
7.2.6
Pulse time
Output
options
Resound on new
alarm
7.2.7
Fault delay time
Mains
power
60
Smart Infrastructure

User interface

If selected, the lamp test function is only available at access level 2.
Otherwise it is available at access levels 1 and 2.
If selected, all sounder control lines can be activated by pressing
the button <Silence / resound> if access level 2 is achieved.
If selected, all sounder lines can be silenced by <ACK>.
If selected, the button function <ACK> is available in access level 1
in addition to the access level 2.
If selected, the LED is activated when the output 'Alarm dialer' is
active. Otherwise, the LED is activated by general alarm.
If selected, the LED is activated if the dialer device confirmation
signal is given.
Standard: Fulfills EN 54-2
UK only FC122: 4 zones without customer text are displayed.

Zone options

The fire condition is achieved with the second detector activation in
the same zone only. The inhibit time, between the first and the
second activation can be set to from 15 to 60 seconds. The higher
the value, the more reliable the application.

Output options

Fire alarm: Select the time for switch on / off for the respective
outputs. Value range : On 0 - 3 sec. Off 0 - 5 sec.
Alert: Select the time for switch on / off for the programmed outputs.
Value range: On 0 - 3 sec. Off 0 - 5 sec.
If selected, the sounder line will resound with a new alarm.

Mains power

Delay time for Mains power fault. Time delay up to 30 min. selectable
in 5 min. steps.
A6V10393190_h_en_--