Standard And Options En 54 - Siemens FC121-ZA Technical Manual

Fire control panel
Hide thumbs Also See for FC121-ZA:
Table of Contents

Advertisement

3.4
EN 54-2 Definitions
7.8
Output to fire alarm device
EN 54-1 / C
7.9.1
Output to fire alarm routing equipment
EN 54-1 / E
7.9.2
Alarm confirmation input from fire
alarm routing equipment
7.10.1
Outputs to fire protection equipment
EN 54-1 / G
7.11.1
Delays to outputs V1 / V2 timer for
alarm organization
7.11.2
Switch on /off delays to outputs, V1 /
V2 timer for alarm organization
7.12.1
Dependencies on more than one
alarm signal.
Type A dependency from the same
detector, or another in the same zone
7.12.2
Dependencies on more than one
alarm signal
Type B dependency cross zoning
7.13
Alarm counter
(option with requirement)
8.8
Output to fault warning routing
equipment
8.9
Output to fault warning routing
equipment according EN 54-1 / J
10
Test condition
(option with requirements)
EN 54-13 Definitions
5.3.4.2
Open and short circuit on a
transmission path
Smart Infrastructure

Standard and options EN 54

The fire control panel is designed to comply with the requirements of EN 54 part 2 / 4.
The EN 54-2 options are fulfilled if the following
configurations are used.
Installation
Configuration / Operation
Monitored output
Sounder control
e.g. OUT 1
Monitored output
Alarm dialer
e.g. OUT 2
Input
Dialer device confirmation
signal; LED fire brigade
activated via input
Fire output
Monitored output
e.g. OUT 4
Alarm Verification Concept;
Manned / unmanned
Button 'Manned/unmanned'
Detector coincidence inhibit
time 15 - 60 sec.
Reset of the first alarm after
90 sec.
Zone coincidence
(= cross zoning)
Alarm counter
Relay output
Fault dialer
e.g. OUT 3
Monitored output
Fault dialer
e.g. OUT 4
Test zone
The EN 54-13 standard is achieved, if the following
system functions are fulfilled:
Installation
Zone mode 'standard'
Outputs card supervised
Card 1, OUT A / B: 4 / 5
Card 2, OUT A / B: 8 / 9
Card 3, OUT A / B: 12 / 13
Fault dialer
Card 1, OUT A: 4
Card 2, OUT A: 8
Card 3, OUT A: 12
Chapter
7.1.2
6.4.2
7.2.6
7.1.2
7.2.4
7.1.3
7.2.4
7.1.2
6.1.3
7.2.10
6.4.1
7.2.10
7.1.1
7.2.5
7.1.1
6.3.3
7.4
7.1.2
7.1.2
6.4.8
Chapter
7.1.1
4.4.2
7.1.2
4.4.4
17
A6V10393190_h_en_--
2019-09-01