Dialer connection

The FC12x fire control panel provides 'monitored' and 'supervised' dialer connections:
Application 1
-
'Alarm dialer' output (OUT2) monitors the line to the dialer.
-
'Fault dialer' output (OUT3) has no line monitoring to the dialer.
(Does not fulfill chapter 8.9 in EN 54-2)
Programming:
Configure g Outputs g Output 2 g Alarm dialer g
-
Activation condition 'General Alarm'
Configure g Outputs g Output 3 g Fault dialer g Activation condition 'Any fault'
-
Application 2
-
'Alarm dialer' output (OUTB) supervises the line to the dialer.
-
'Fault dialer' output (OUTA) supervises the line and the build in relay of the dialer.
The relay takes over EOL element functionality, if the resistance is between 200-
1000 Ω.
Programming:
Configure g Outputs g Output 5 g Alarm dialer g
-
Supervision EN 54-13 / Calibrate line / Activation condition 'General Alarm'
Configure g Outputs g Output 4 g Fault dialer g
-
Supervision EN 54-13 / Calibrate line / Activation condition 'Any fault'
Dialer
Application 1
(1) Dialer device confirmation signal
As an option, the panel can receive the dialer activation if desired.
The output 'fault dialer' is closed (Inverse function) in quiescent mode.
In case of fault, the output opens.
FC12x
Application 2
Dialer
(1)
Ω ~
Ω
200
1000
29
A6V10393190_h_en_--
2019-09-01