Output - Siemens FC121-ZA Technical Manual

Fire control panel
Hide thumbs Also See for FC121-ZA:
Table of Contents

Advertisement

7.1.2
Configure the output parameters.

Output

Select an output for programming.
Output
1..n
Sounder control
Mode
Alarm dialer
Fault dialer
Fire output
EVAC Sounder NL
Supervision
Enables supervision, creeping open and short for the outputs: 4, 5, 8, 9, 12 and 13.
EN 54-13
The line calibration is needed to achieve supervision. As a result of the calibration the line
Calibrate
resistance is indicated and can be proved using your own calculation.
line
This option is only availible on output cards and if supervision is set.
General Alarm
Activation
*
condition
Active by zone alarm
General Alert
Active by zone alert
Alert by ext. input
Any isolation
Any fault
Manned mode
activated
Alarm dialer fault
Dialer device
confirmation signal
V1 / V2 is running
(SE function)
* Options available depending on the selected mode.
Pulse
This option is available in Alarm and Alert state.
time
Default on 0.5 sec. off 0.5 sec. Details see chapter 7.2.6.
56
Smart Infrastructure
Output
Sounder control is used to activate sounder lines.
(EVAC module replaces 'sounder control' with 'EVAC sounder NL'.)
Alarm dialer is used to transmit the fire alarm to the intervention
force, e.g. fire brigade.
Fault dialer is used to transmit the fault signal to the intervention
force, e.g. service provider.
Fire outputs are used to activate / deactivate controls,
e.g. door holders, lifts, air-condition, etc.
EVAC sounders are used to activate sounder lines.
This option is available if the EVAC module is implemented.
Output is activated if the alarm condition is fulfilled:
Zone 'Direct' is activated, V1 / V2 is expired, cross zoning 2
activated.
Output is activated if the selected zone(s) is in alarm.
Output is activated if cross zoning 1
is running.
Output is activated if the selected zone(s) is in alarm by cross zoning
st
1
zone or V1 / V2 time is running.
Output is activated if one input is activated and programmed as
'activate alert mode'.
Output is activated if any isolation is set.
Output is activated if any fault condition occurs.
Output is activated if manned mode is activated.
Output is activated if the alarm dialer fault via input is in fault condition.
Output is activated if the programmed input is activated.
Output flash during V1; Output on during V2.
st
zone is in alarm or V1 / V2 time
A6V10393190_h_en_--
nd
zone is
2019-09-01