Programming; Configure; Zone - Siemens FC121-ZA Technical Manual

Fire control panel
Hide thumbs Also See for FC121-ZA:
Table of Contents

Advertisement

7
7.1

Configure

7.1.1
Configure parameter for each zone.

Zone

Select a zone for programming.
Zone 1..n
Standard
Mode
Mixed MCP & det.
GB continuity
Short = alarm
Direct
AVC
Via V1 / V2
Via AVC timer
MCP direct
*Device
If selected, the 'Alarm' state is achieved, if the second device activation in the same zone
coincidence
occurs within 90 seconds. The first device activation is inhibited from the zone and
automatically reset after a defined time, (default value: 15 second, see chapter 7.2.5).
Zone
If selected, the 'Alarm' state is achieved, if the second corresponding zone is in 'Alarm' as well.
coincidence
The zone pairs (1&2, 3&4, 5&6, etc) are predefined in the system,
e.g. if zone 6 is selected, zone 5 is automatically linked as well and vice versa.
Customer
Name the zone, see chapter 7.5.
text
Smart Infrastructure

Programming

For programming, access level 3 is required.
All outputs are automatically isolated during programming mode.
All disabled outputs are automatically enabled if access level 2 is reached.
Configure
Zone
Output
Zone
Automatic detectors
and manual call
points can be mixed
within the same
zone.
Device could be
either conventional
or collective.
No delay, immediate alarm.
'1'
'2'
Delayed alarm.
- Delayed alarm for automatic
detectors.
'3'
- No delay for MCPs.
*Do NOT use this function in combination with FDOOT241-9 (ES<13). For detailed
information refer to document A6V10393192.
Accessory
Input
card(s)
AVC option
'1', '2'
If detectors are removed, the
AVC option
zone will work properly.
'1', '2', '3'
Any short is detected as 'Fire
Alarm'.
V1: reaction time, 3 min.
V2: investigation time, 5 min.
(Change value, see
chapter 7.2.10).
55
A6V10393190_h_en_--
2019-09-01