Controller Settings Tab - Trane Tracer Uc

Programmable bacnet controller for variable-air-volume (vav) units
Table of Contents

Advertisement

Tracer™ UC400 Controller Operations
Edit an Existing Point
Use the Analog, Binary, and Multistate tab screens on the Controller Settings button to edit point
definitions.
1. Click the Analog, Binary, or Multistate tab.
2. Select the check box on the left side the row of the point to edit.
3. Select the Edit option from the Action drop-down menu. The appropriate Point Configuration
4. Edit the desired individual settings. (Click Help to see descriptions of the various controls.)
5. Click Save when finished to save the point or points to the existing points file on the PC hard

Controller Settings Tab

The Controller Settings tab contains drop-down lists and options to select some controller and
display settings. The content of this screen is dynamically generated depending on the type of
controller to be connected to and the system protocol used to communicate with the controller.
Date and Time
Displays the current date and time from the controller.
1. Click the Date and Time expanding box.
2. Select the preferred settings using the Date and Time boxes.
3. Click Save to save selections
Units
Units of Measure
1. Click the Units expanding box.
2. Select the preferred Number Format from the Number Format drop-down list.
3. Select the preferred units of measure by clicking either the I-P (Inches and Pounds) or SI
4. Check the Modify Default Units check box to change the default units of measure (if desired) for
5. Modify any of the default units by selecting the appropriate option from the drop-down lists in
6. Click Save.
38
dialog box displays.
drive.
Number Format: Use this drop-down list to choose from available number formats for data
display.
Default Units: Use these option buttons to indicate which measurement system to use: I-P
(inches and pounds) or SI (Standard International Units).
Modify Default Units: Use these drop-down lists to change the default units of measure
displayed for various device inputs or capabilities, such as Temperature, Gaseous Pressure,
Fluid Pressure, Cooling Capacity, and so on.
(Standard International Units) option button in the Default Units group box.
various device inputs or capabilities, such as Temperature, Gaseous Pressure, Fluid Pressure,
Cooling Capacity, and so on.
the Modify Default Units group box.
VAV-SVX07B-EN