Overview
Device Connections
The following table provides information about the types of device connections.
Connection
Quantity
Analog input
5
(AI1 to AI5)
Universal input
2
(UI1 and UI2)
Binary input (BI1 to
BI3) See CAUTION
below.
3
!
3
Binary output (BO1
to BO3) See
CAUTION below.
Other
!
Ranges
Binary output (BO4
to BO9) See
CAUTION below.
6
!
Analog output/
binary input
2
(AO1/BI4 and
AO2/BI5)
Pressure inputs
2
(PI1 and PI2)
Overall Point Total
23
Electrical Hazard!
Do Not mix Class 1 and Class 2 voltage wiring in an enclosure or on a controller without an approved barrier
between the wiring.
10
Types
Range
Temperature
10 kthermistor
Setpoint
189 to 889
Resistive
100 to 100 k
Linear
0–20 mA
Linear
0–10 Vdc
Temperature
10 kthermistor
Setpoint
189 to 889
Resistive
100 to 100 k
Binary
Open collector/dry contact
Pulse
Solid state open collector
24 Vac detect
Relay
2.88 A @24 Vac pilot duty
• General purpose
• 10 A max up to 277 Vac
(resistive)
• 10 A max up to 30 Vdc
• Motor duty
• 1/3 hp @125 Vac (7.5 A max)
(inductive)
• 1/2 hp @277 Vac (7.5 A max)
0.5 A max @24-277 Vac, resistive
TRIAC
and pilot duty
Linear output
0–20 mA
Linear output
0–10 Vdc
Binary input
Dry contact
PWM output
80 Hz signal @ 15 Vdc
3-wire
0–5 in H
2
CAUTION
Notes
AI1 to AI4 can be configured for timed override
capability.
Typically used for fan speed switch.
These inputs may be configured to be thermistor or
resistive inputs, 0–10 Vdc inputs, or 0–20 mA inputs.
Low impedance relay contacts recommended.
Minimum dwell time is 25 ms On and 25 ms Off.
The UC400 controller provides the 24 Vac that is
required to drive the binary inputs when using the
recommended connections.
Power needs to be wired to the binary output. All
outputs are isolated from each other and from ground
or power. Ranges given are per contact.
Use for modulating TRIAC. User determines whether
closing high side (providing voltage to the grounded
load) or low side (providing ground to the power load).
Ranges given are per contact and power comes from
TRIAC SUPPLY circuit.
Each termination must be configured as either an
analog output or binary input.
Pressure inputs supplied with 5 volts of power.
O
Designed for Kavlico™ pressure transducers.
VAV-SVX07B-EN