Wiring Installation

BACnet MS/TP Communication Link

This section provides information about the following:
For more details about BACnet MS/TP communication link, refer to the BACnet MS-TP Wiring and
Link Performance Best Practices and Troubleshooting Guide (BAS-SVX51).
Electrocution and Fire Hazards with Improperly Installed and Grounded
Field Wiring!
Improperly installed/grounded field wiring poses FIRE & ELECTROCUTION hazards. To avoid
these hazards, the user MUST follow requirements for field wiring installation and grounding
as described in NEC and local/state electrical codes. All field wiring MUST be performed by
qualified personnel. Failure to follow these requirements could result in death or serious injury.

Wiring Guidelines

16
"Wiring Guidelines"
Use 18 AWG Trane purple-shielded communication wire for BACnet installations.
Link limit of 4,000 ft and 60 devices maximum (without a repeater).
Use a Trane BACnet termination on each end of the link.
Use daisy chain topology (refer to
Maintain polarity.
WARNING
Figure 1, p.
17).
VAV-SVX07B-EN