Wiring Installation
BACnet MS/TP Communication Link
This section provides information about the following:
•
•
•
•
•
•
•
•
•
For more details about BACnet MS/TP communication link, refer to the BACnet MS-TP Wiring and
Link Performance Best Practices and Troubleshooting Guide (BAS-SVX51).
Electrocution and Fire Hazards with Improperly Installed and Grounded
Field Wiring!
Improperly installed/grounded field wiring poses FIRE & ELECTROCUTION hazards. To avoid
these hazards, the user MUST follow requirements for field wiring installation and grounding
as described in NEC and local/state electrical codes. All field wiring MUST be performed by
qualified personnel. Failure to follow these requirements could result in death or serious injury.
Wiring Guidelines
•
•
•
•
•
16
"Wiring Guidelines"
Use 18 AWG Trane purple-shielded communication wire for BACnet installations.
Link limit of 4,000 ft and 60 devices maximum (without a repeater).
Use a Trane BACnet termination on each end of the link.
Use daisy chain topology (refer to
Maintain polarity.
WARNING
Figure 1, p.
17).