Bacnet Networks Without A Tracer Sc System Controller; Bacnet Networks With A Tracer Sc System Controller - Trane Tracer Uc

Programmable bacnet controller for variable-air-volume (vav) units
Table of Contents

Advertisement

BACnet Networks Without a Tracer SC System Controller

On BACnet networks without a Tracer SC system controller, the Device ID can be assigned one of
two ways:

BACnet Networks With a Tracer SC System Controller

On BACnet networks with a Tracer SC system controller, the Device ID for the UC400 controller is
always soft set by the system controller using the following scheme (refer to the illustration below).
Note: The BACnet Device ID is displayed as the Software Device ID on the Tracer TU Controller
VAV-SVX07B-EN
It can be the same number as the MAC Address, determined by the rotary address dials on the
UC400 controller. For example, if the rotary address dials are set to 042, both the MAC Address
and the BACnet Device ID are 042, OR
It can be soft set using Tracer TU service tool. If the BACnet Device ID is set using Tracer TU
service tool, the rotary address dials only affect the MAC Address, they do not affect the BACnet
Device ID. For more details, refer to the Tracer™ UC400 Controller BACnet Protocol
Implementation Conformance Statement (PICS) [BAS-PRG007-EN].
Settings Page in the Protocol group.
Tracer SC
ADDRESS
x100
x10
0
0
The first three digits are
determined by the address
rotary dials on the Tracer
SC system controller.
x1
1
2
The last three digits are
determined by the rotary
address dials on the
UC400 controller.
The fourth digit is
determined by the link
number to which the UC400
controller is attached.
Wiring Installation
Tracer UC400
UC400
ADDRESS
x100
x10
x1
0
0
1
BACnet Device ID
For This UC400
= 0012001