Trane Tracer Uc page 23

Programmable bacnet controller for variable-air-volume (vav) units
Table of Contents

Advertisement

Zone Sensor Mounting and Wiring
Mounting Location
A zone sensor in each control zone should be located in the most critical area of the zone. Sensors
should not be mounted in direct sunlight or in the area supply air stream. Subdivision of the zone
may be necessary for adequate control and comfort. Avoid mounting zone sensors in areas subject
to the following:
Wiring
Each unit must be controlled by a zone sensor that utilizes a standard 10K at 77°F thermistor for
temperature outputs. Field wiring for the zone sensors must meet the following requirements:
Important: Control wires and power conductors can never be near each other (except at 90
Zone Sensor Communication Stubs
The wire that runs from a zone sensor to a unit controller is commonly referred to as the
communication stub. It is the wire that goes from the IMC terminal link on the UC400 controller
down to the zone sensor. At least one zone sensor per area or controller network should include
the optional communications module. Installing additional sensors with the communications
module provides added convenience for the service technician.
Important: There is no limitation on the number of stubs that can be wired from the UC400
The wire for the communication stub must be the same that is used for BACnet communication link
wiring. Refer to the section,
VAV-SVX07B-EN
Wireless zone sensor with digital display
– Sensor/Receiver Set; Part Number X1379082401
– Sensor only; Part Number X1379082201
Wireless receiver only; Part Number X13790854
Drafts or dead spots behind doors or corners.
Hot or cold air ducts.
Radiant heat from the sun or appliances.
Concealed pipes or chimneys.
Surfaces not heated or cooled behind the sensor such as outside walls.
Airflows from adjacent zones or other units.
Avoid locations outside of the operating temperature and the humidity range.
Use 18 to 22 AWG stranded, tinned-copper, shielded, twisted-pair wire, recommended.
Maximum wire length 300 ft. (91 m).
All wiring must be in accordance with the NEC and local codes.
If local codes require enclosed conductors, install the zone sensor wires in the conduit.
Refer to
"Appendix: Typical Trane Factory Wiring Diagrams, " p.
degrees). Do not run power wired through same conduit as signal wires.
controller. Polarity must be maintained and the length limit is 300 ft (91 m).
"Zone Sensor Mounting and Wiring, " p.
Wiring Installation
77.
23.
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tracer uc400

Table of Contents